Voltage Drop Calculator

Wire Has Resistance Too

Copper conductors aren't perfect conductors — every foot of wire has a small amount of resistance, and over a long run that resistance quietly eats into the voltage that actually reaches the load. A circuit that measures perfectly at the panel can still leave a motor or appliance underpowered at the far end of a long run. This calculator applies the standard voltage-drop formula to a chosen wire gauge, length, and current so the loss can be checked before installation rather than discovered afterward.

The Formula

Vdrop = Multiplier × Length × Current × (Ohms per ft)
Percent Drop = (Vdrop / Source Voltage) × 100

The multiplier accounts for the return path: single-phase circuits use 2 (current travels out and back through the conductor), while three-phase circuits use √3 ≈ 1.732. Conductor resistance per foot is drawn from standard copper wire tables.

Copper Conductor Resistance by Gauge

Approximate copper conductor resistance (ohms per 1000 ft)
Wire Gauge (AWG)Ohms per 1000 ft
142.525
121.588
100.999
80.628
60.395
40.249
20.1563
1/00.0983
2/00.0779
4/00.049

A Worked Example

A 100-foot single-phase run of 12 AWG copper carrying 20 A from a 120 V source:

Single-phase vs. three-phase voltage drop, same run
ConfigurationVoltage DropPercent Drop
Single-phase (multiplier 2)6.352 V5.29%
Three-phase (multiplier √3)5.501 V4.58%

Both exceed the commonly recommended 3% maximum — this run would call for a heavier gauge or a shorter path.

Where This Calculation Matters

  • Long outbuilding or subpanel runs — feeding a detached garage or barn often means hundreds of feet of conductor, where drop adds up fast.
  • Motor performance — motors are sensitive to undervoltage, which can cause overheating and reduced torque even when the load isn't excessive.
  • Code compliance — while not always a hard code requirement, a 3% branch-circuit / 5% combined limit is a widely followed design guideline.
  • Solar and battery wiring — low-voltage DC runs (12V or 24V systems) are especially sensitive to voltage drop percentage-wise.

How to Use This Calculator

  1. Select the wire gauge (AWG) from the dropdown.
  2. Enter the one-way run length in feet.
  3. Enter the current the circuit will carry, in amps.
  4. Enter the source voltage.
  5. Select Single-Phase or Three-Phase, then select Calculate.

Related Calculations

Not sure the gauge is adequate to begin with? Start with the Wire Size Calculator, or check total circuit demand with the Electrical Load Calculator.