Airflow CFM Calculator

Heat, Airflow, and Temperature Rise Are Locked Together

The same BTU/hr of heating or cooling capacity can be delivered by a small volume of air at a large temperature swing, or a large volume of air at a gentle one — and HVAC designers use the standard sensible heat formula to move between the two. This calculator rearranges that formula to find the airflow, in CFM, required to deliver a known heat load at a chosen supply-to-room temperature difference.

The Formula

BTU/hr = 1.08 × CFM × Delta T
CFM = BTU/hr / (1.08 × Delta T)

1.08 is the standard sensible heat factor for air at sea-level density and specific heat, combining air's density and specific heat capacity into a single constant. Delta T is the temperature difference, in °F, between supply air and room air.

A Worked Example

36,000 BTU/hr load at a 20°F delta T
InputValue
Heat Load36,000 BTU/hr
Delta T20°F
Required Airflow1,666.7 CFM

CFM = 36,000 ÷ (1.08 × 20) = 1,666.7 CFM.

Where This Calculation Matters

  • Blower and equipment selection — confirming a unit's rated CFM output can deliver the required airflow at a realistic delta T.
  • Duct system design — the CFM figure this produces is the direct input to duct sizing for each branch.
  • Diagnosing comfort complaints — a system delivering less CFM than required at its design delta T will underperform even if the rated tonnage looks adequate on paper.
  • Commissioning and balancing — technicians compare measured CFM against the calculated requirement when balancing airflow to each room.

How to Use This Calculator

  1. Enter the Heat Load in BTU/hr.
  2. Enter the Temperature Difference (Delta T) in °F between supply and room air.
  3. Select Calculate to see the required airflow in CFM.

Related Calculations

Turn the resulting CFM into a duct size with the HVAC Duct Sizer Calculator, or check how many air changes per hour that airflow produces with the Air Changes Per Hour Calculator.