Boiler Blowdown Flash Steam Recovery Calculator
Boiler Blowdown Flash Steam Recovery Calculator
When high-pressure boiler blowdown water drops into a lower-pressure flash tank, some of it instantly turns to steam - simply because that water was carrying more energy than liquid water can hold at the lower pressure.
The Formula
Flash % = (h1 - hf2) / hfg2 × 100
Worked Example
Blowdown enthalpy 900 kJ/kg, flash tank saturated liquid enthalpy 419 kJ/kg, flash tank latent heat 2,257 kJ/kg: Flash % = (900-419)/2257 × 100 ≈ 21.3%.
How to Use This Calculator
- Enter the blowdown water's enthalpy at boiler pressure.
- Enter the saturated liquid enthalpy at the flash tank's (lower) pressure.
- Enter the latent heat of vaporization at the flash tank pressure.
This recoverable flash steam can be routed to a deaerator or low-pressure steam system rather than wasted, making blowdown heat recovery a genuine efficiency opportunity many facilities overlook.